Customer says: "the new heater is not as hot as the old one." We measure at the heater terminals and it reads 195V instead of 220V. The cable is too thin for the distance.
The formula
Voltage drop = 2 x length (m) x current (A) x 0.0175 / cable area (mm2). (0.0175 is copper resistivity.)
Example: 30 meter run, 20A heater, 2.5 mm2 cable. Drop = 2 x 30 x 20 x 0.0175 / 2.5 = 8.4V. That is 3.8% drop - acceptable.
Same run on 1.5 mm2: drop = 14V. Heater sees 206V, power drops 12%.
The 3% rule
Keep voltage drop under 3% of rated voltage. For 220V that is 6.6V. For 380V that is 11.4V. Above that, the heater loses power and the cable gets warm.
A warehouse in Tianjin had a 9 kW duct heater 40 meters from the panel. They used 2.5 mm2 wire. At the heater, voltage was 190V. We upgraded to 6 mm2. Voltage at the heater was 218V. Heat-up time dropped from 40 minutes to 25.
Three phase note
For three phase, voltage drop = 1.732 x length x current x 0.0175 / area. Three phase has less drop because current is lower.