Grounded vs Ungrounded Thermocouple Tip: Fast or Isolated?

Thermocouples come with the tip welded to the sheath (grounded) or insulated inside (ungrounded). Most people do not know the difference.

Grounded tip

The measuring junction is welded to the metal sheath. Response time is fast (1 to 2 seconds). But the sheath is electrically connected to the thermocouple wires. If the sheath touches a grounded tank, you get a ground loop and noise in the reading.

Use it for: air and gas measurement, dry surfaces, where speed matters and there is no electrical noise.

Ungrounded (isolated) tip

The junction floats inside the MgO, not touching the sheath. Response is slower (3 to 5 seconds). But the wires are fully isolated from the sheath. No ground loop, no noise.

Use it for: liquid immersion, electric heater ducts, anywhere the sheath touches metal and there is SSR or VFD noise.

A customer's oven temperature read jumped 5 C randomly. We found the grounded thermocouple tip was touching the heater sheath, and the SSR switching noise was feeding back into the thermocouple. Swapped to ungrounded. Reading steady.

Need thermocouples for noisy heater circuits?

We ship ungrounded tips on any heater with SSR control.

Send Your Specs