Star vs Delta Heater Wiring: Why It Matters

Three phase heaters have three elements. You connect them in star or delta. The same heater runs at 3 different power depending on how you wire it.

Star (Y) connection

One end of each element ties together at the neutral point. The other ends go to L1, L2, L3. Each element sees 220V (phase voltage). Total power = 3 x (220^2 / R).

Delta connection

Elements connect in a triangle. Each element sees 380V (line voltage). Total power = 3 x (380^2 / R). That is 3 times the star power.

Same 9 kW heater wired in star on 380V three phase only puts out 3 kW. Wire it in delta and it does 9 kW. We have seen customers melt connectors because they wired a delta heater in star - the heater drew 3x current trying to get full power.

How to tell which you have

Look at the terminal block on the heater. Six terminals (T1 T2 T3 U V W). If you see three copper bars tying T1-U, T2-V, T3-W together, that is delta. If there is a separate neutral bar tying U V W together, that is star.

Rule of thumb

Need help wiring three phase heaters?

Send us a photo of your terminal block. We will tell you star or delta.

Send Your Specs
Get a Quote