A solid state relay (SSR) switches power using semiconductors, not mechanical contacts. No click, no arc, no wear. That is why every PID oven uses one.
How it works
3 to 32V DC control signal turns on a triac or SCR inside. It switches 220V or 380V AC load. Input and output are optically isolated - 2500V between them.
Why SSR beats contactors
- Silent - no click in the factory
- Fast switching - millisecond response, good for PID control
- Wears out - no mechanical contacts to burn
- Can switch 100,000 times per day without failure
But they get hot
An SSR drops about 1V across itself when on. At 40A that is 40W of heat. Without a heat sink, the SSR dies in minutes. We always mount SSRs on an aluminum heat sink, with a cooling fan above 25A.
A customer in Foshan used SSRs without heat sinks. They lasted 2 weeks. We sent them heat sinks with thermal paste. Same SSRs, running 3 years now.
Sizing rules
- Choose SSR current rating at least 2x the heater current. Inrush current on cold nichrome wire is 1.5x running current.
- Use a snubber circuit (RC) on inductive loads. Heaters are resistive, but contactors and coils need it.
- Keep control wires away from load wires - the triac can false trigger from noise.
Need SSR relays for your heater control?
Tell us heater current and voltage. We size the SSR and heat sink.