We build heaters in Yangzhou, China. Every week we get calls: "my heater burned out after three months" or "it can't reach temp." Most of the time it's not a bad heater — it's a sizing mistake. Here's how we actually calculate.
The quick air heater formula
For duct and pipeline air heating, the shortcut every Chinese factory uses:
Power (kW) = Airflow (m³/h) × Temperature rise (°C) × 0.00033
Example: 5000 m³/h airflow, need 40°C rise. 5000 × 40 × 0.00033 = 66 kW. Then add 15–20% margin for duct loss and cold startup → order a 75 kW unit.
That 0.00033 already bakes in air density (1.2 kg/m³), specific heat (1.005 kJ/kg·°C) and a rough efficiency factor. You don't need to re-derive it every time.
For liquid heating
Water or oil: P (kW) = flow rate (kg/h) × specific heat × ΔT ÷ (3600 × 0.95). Add 10–20% margin on top.
Water specific heat ≈ 4.2 kJ/kg·°C. Thermal oil ≈ 2.0 kJ/kg·°C. Don't mix those up — using 4.2 for oil gives you a heater twice as big as you need.
Watt density is where elements die
Power gets all the attention. But what actually kills a tube is surface load (W/cm²) — how much heat you're pushing through every square centimeter of sheath.
- Clean water: 8–15 W/cm² max
- Light oil (heating oil, diesel): 2–4 W/cm²
- Heavy oil / viscous fluid: 1–2 W/cm²
- Forced air flow (≥8 m/s): 2–5 W/cm²
- Still air / dry firing: under 1 W/cm², or it glows red and oxidizes
If you oversqueeze power into a small bundle, the sheath runs hot, the MgO dries out, and the resistance wire corrodes. We've seen 304 tubes pitch black and carbonized in 3 months on an oil tank because someone ran 8 W/cm² on heavy oil.
The minimum flow problem
Everybody sizes for maximum flow. Nobody checks minimum flow. That's where the heater self-destructs — when flow drops, the sheath can't dump its heat, local temperature spikes, and you get a burnout.
Two non-negotiable accessories:
- Flow switch — cuts power if flow drops below setpoint
- High-limit thermostat — independent safety that trips at max allowable sheath temp
Pressure rating matters too
Duct heaters are basically atmospheric — 0.05 MPa max, flanged to a square duct. Pipeline heaters for gas must be pressure-rated. Common ratings are 1.0 MPa, 1.6 MPa, up to 6.4 MPa for high-pressure gas. Tell us the working pressure — we'll size the shell wall and flange accordingly.
Send us your numbers
Airflow or flow rate, inlet/outlet temp, fluid, voltage and pressure. We'll send back a sizing sheet and drawing within 24 hours — no obligation.