MI cable looks like a solid metal tube. People bend it like copper pipe and then wonder why it goes to ground.
Minimum bend radius
- 3.2 mm diameter: 25 mm minimum (8 x OD)
- 4.8 mm: 35 mm minimum
- 6.4 mm: 50 mm minimum
Below that, the compacted MgO powder cracks. Cracks fill with moisture from the air, insulation resistance drops, and the cable leaks to ground.
How to bend it right
Use a tube bender or a coil spring. Do not hand bend tight corners. Do not hammer it into place. If you need a 90 degree turn, use a mandrel or pre-bent factory section.
A project in Heilongjiang had MI cable freeze protection on pipe. The installer bent it 180 degrees by hand at 50 mm radius on 6.4 mm cable. Three months later, 4 out of 20 circuits failed insulation test. We had to dig it up and replace.
After bending
Test insulation resistance with a 500V megger before energizing. Should read above 100 M ohm. If it reads low, the MgO absorbed moisture - heat the cable with a heat gun for 30 minutes and retest.