A customer in Heilongjiang needed freeze protection on outdoor pump houses. Winter hits -30°C. He tried self-regulating plastic heating cable first. It died in one winter — the outer jacket cracked from cold, moisture got in, and it shorted.
We built him MI (mineral-insulated) cable runs. Stainless sheath, magnesium oxide inside. Three years later he called: "still works."
What MI cable actually is
Inside a stainless steel tube, MgO powder compacts the resistance wire. No air gap, no plastic, no glue. You can submerge it, bury it in concrete, bend it around fittings, wash it down with chemicals. It's rated for continuous 600°C, and it's waterproof and explosion-proof.
It costs more per meter than plastic heating cable. But plastic cable tops out around 150°C. MI goes to 600°C. That's a different category.
Where we specify MI
- High-temp trace heating — pipelines above 150°C, reaction vessels, where plastic cable melts
- Freeze protection outdoors -30°C to -40°C, buried or exposed, where plastic jackets crack
- High-vibration areas — pumps, compressors, marine shafts, where plastic cable fatigues and breaks
- Chemical washdown — food plants, pharma plants where plastic gets eaten by cleaners
- Hazardous areas — oil and gas, where explosion-proof rating matters
- Nuclear, food-grade, cleanroom — no outgassing, no plastic, all metal
The catch: don't kink it
MI cable is stiff. You can bend it, but the minimum bend radius is 6× the cable diameter. Kink it tighter and the MgO powder fractures — now there's an air pocket around the resistance wire, it overheats locally, and it burns out.
Also: end seals must be compression fittings, not epoxy. Epoxy lets moisture creep in over time. We ship MI cable with sealed compression glands on both ends, and the cold section (non-heating tail) clearly marked.
Plastic heating cable costs 20 RMB/m. MI cable costs 80–150 RMB/m. But if your plastic cable dies in 18 months and MI lasts 15 years, the math flips. We've replaced more dead plastic trace heating runs than we can count.
What we ship
We build MI cable to your drawing: length, voltage, watt density, cold-end length, terminal type. Stainless sheath 304 standard, 316L for coastal or chemical. We can ship straight, coiled, or pre-bent to your pipe layout.
Need MI cable for trace heating?
Tell us the length, voltage, max temperature and what you're tracing. We'll quote within 24 hours.
Get an MI Cable Quote