Inside a tubular heater, the nichrome wire is surrounded by MgO powder. If the wire shifts and touches the metal sheath, the whole tank becomes live. Without a ground, the first person to touch it gets the shock.
How grounding works
The heater metal sheath connects to a green-yellow ground wire back to the panel. If the wire touches sheath, current flows through the ground path. The breaker or RCD trips. Nobody gets hurt.
What we see in the field
- Customer did not connect the ground wire "because it was working"
- Tank painted, ground lug painted over, no contact
- Ground wire too thin - 1 mm2 for a 50A heater
A food plant in Guangdong had a stainless tank heater. The ground wire was loose. A worker touched the tank and got thrown across the room. We re-grounded with 4 mm2 wire and tested continuity. No repeat.
Ground wire size
- Up to 16A circuit: 1.5 mm2 ground
- 16 to 63A: 2.5 mm2
- 63 to 200A: 6 mm2
Test ground continuity every year. Should read under 0.1 ohm from heater flange to panel ground bar.