Duct heaters are sized for a minimum airflow. Cut the airflow in half and the sheath temperature doubles. The elements glow cherry red and burn open.
Minimum airflow rules
- Still air duct heater: 1.5 m/s minimum face velocity
- Process air heater: 3 m/s minimum
- High temperature duct: 5 m/s above 300 C
Filter maintenance
The inlet filter collects dust, lint and factory dirt. When it clogs, static pressure rises and airflow drops. We recommend:
- Check filter pressure gauge monthly
- Replace when differential pressure hits 250 Pa
- In woodworking or textile shops, check weekly
A paint shop in Suzhou ran a 30 kW duct heater. The filter was 3 months overdue. The elements overheated and the finned sheath warped. New elements cost 18000 RMB. A 200 RMB filter would have prevented it.
Airflow switch
Every duct heater should have a pressure switch on the inlet. If airflow drops below setpoint, it cuts power to the elements. Cheap insurance, 200 RMB part.