Customers call us and say 'I need a duct heater for 1000 CFM'. That is not enough info. We need three numbers: airflow, inlet temperature and target outlet temperature. The kW then falls out of a simple formula.

The basic formula

kW = (CFM x delta-T x 1.08) / 3000 for imperial units. In metric: kW = (m3/h x delta-T x 0.33) / 1000. For 2000 m3/h airflow heating from 20 C to 80 C (60 C rise): 2000 x 60 x 0.33 / 1000 = about 40 kW.

Pressure drop matters too

A customer in Suzhou complained his oven was weak after we installed a 30 kW duct heater. Turns out the heating elements added 200 Pa pressure drop to a fan that was only sized for 80 Pa. We added a bypass damper and upsized the fan. Always check pressure drop against your fan curve.

Leave 20 percent margin

Never run a duct heater at 100 percent duty. We size it so the controller runs at 70 to 80 percent. That leaves room for dirty filters, cold mornings and future upgrades.