Every electric heater circuit needs a switch. The two choices are a magnetic contactor or a solid state relay (SSR). They do the same job but cost and life are different.
Magnetic contactor
An electromagnet pulls contacts together. Audible click. Handles 9A to 1000A. Costs 50 to 200 RMB. Mechanical life is about 10 million operations.
Best for: big heaters over 15 kW, infrequent switching (a few times per day), rough factory environment.
Solid state relay
No moving parts. Silent. Handles 10A to 100A per unit. Costs 80 to 300 RMB. Semiconductor life is effectively unlimited, but they burn out without a heat sink.
Best for: PID control where it switches every second, quiet areas, small to medium heaters under 15 kW.
A customer ran a 6 kW oven with a contactor on PID. It clicked 10 times a minute and the contacts welded shut after 6 months. We swapped to a 25A SSR on heat sink. Silent and still running 3 years later.
Rule of thumb
- Switching less than 10 times per hour: contactor is fine
- PID control switching every few seconds: use SSR
- Over 30 kW: contactor (or multiple SSRs in parallel)