People size breakers the way they size motor breakers. Heaters are different - no inrush, no startup spike. But you still need headroom.
The rule
Breaker rating = 125% of full load current. This is the NEC and GB standard for continuous loads. A heater runs for hours, so it counts as continuous.
Examples:
- 10A heater: breaker = 12.5A, use 16A
- 25A heater: breaker = 31A, use 32A
- 45A heater: breaker = 56A, use 63A
Type C or Type D?
Type C breaker trips at 5 to 10x rated current. That is fine for heaters. Type D (10 to 20x) is for motors with high inrush. You do not need D for heaters.
A customer kept tripping a 16A breaker on a 10A heater. We checked - the heater was 10A cold but 15A at startup? No, heaters are resistive, no inrush. The breaker was worn out. New 16A Type C breaker fixed it.
Leakage protection (RCD/GFCI)
For wet areas and immersion heaters, add a 30mA residual current device. If the element grounds out, it cuts power in 30ms before anyone gets hurt.