We see this on every job: customer runs a 15 kW heater on 1.5 mm2 wire. The wire gets warm, the heater runs at 180V instead of 220V, and it takes forever to heat up.
How much current?
Current = Power / Voltage. For single phase: I = P / V. For three phase: I = P / (1.732 x V).
Examples:
- 5 kW / 220V = 23A
- 10 kW / 220V = 45A
- 15 kW / 380V three phase = 23A per phase
Copper cable current ratings
- 1.5 mm2: 15A max
- 2.5 mm2: 20A
- 4 mm2: 25A
- 6 mm2: 32A
- 10 mm2: 45A
- 16 mm2: 60A
Always size cable for 125% of running current. A 23A heater needs 2.5 mm2 rated for 20A? No - go up to 4 mm2.
A 12 kW heater on 220V draws 55A. Customer used 6 mm2 wire (32A rating). The wire got so hot the insulation melted. We replaced with 16 mm2. Wire stayed cool.
Voltage drop
Long runs drop voltage. Rule: voltage drop under 3% at full load. If your heater is 50 meters from the panel, add one cable size.
Need help sizing cable and breakers?
Tell us total kW, voltage and distance. We spec the cable.
Send Your Specs