For a large tank, one tubular element rarely carries enough wattage. A bundle flange heater takes several heated tubes, welds them into a single flange plate, and brings their leads into one junction box. It is the standard build for kW-level immersion heating.
Main parts of the bundle
- Flange plate: matched to the tank nozzle standard, DN and pressure class
- Heating tubes: straight, U-shaped or serpentine, arranged to cover the tank area
- Lead exits and terminal block: grouped inside the head enclosure
- Junction box: protects the connections, rated for the site environment
- Optional sensor: thermocouple or RTD sleeve for closed-loop temperature control
Why split the wattage across tubes
Concentrating high kW in one tube pushes the sheath watt density up and shortens life. Spreading the same wattage over several tubes keeps each tube's surface load low, gives more heat-transfer area, and evens out the temperature in the liquid. Tubes are spaced so liquid can circulate between rows instead of being blocked.
Wiring groups and staged control
On bigger bundles the elements are split into electrical groups rather than all running together. Groups can be switched in stages as the tank heats up, which matches contactor capacity and lets the controller trim power instead of running the full bank at once. Phase balance across the groups matters on three-phase supply.
Build checks before shipment
Each tube is checked for resistance to rated kW, insulation is meggered, and the bundle is pressure or leak tested where the application calls for it. The sheath material follows the fluid: stainless for water, Incoloy or treated steel for hot oil and more aggressive liquids.
A bundle is not just several tubes bolted together. Tube spacing keeps circulation alive, wiring groups keep the load balanced, and a low per-tube surface load is what keeps the heater running years instead of months.
Need a bundle built for your tank?
Send tank size, fluid, target temperature, kW and voltage. We will lay out the tube count, spacing and wiring groups to match.
Send Your Requirements